A rewind is not putting copper back into a stator. It is putting the same copper back — same turns, same gauge, same pitch, same connection — and then proving it with a meter.

What we take on

Single-phase and three-phase induction motors from 0.5 HP up to 100 HP: flour mill and chaff cutter motors, monoblock and openwell pump motors, compressor and lathe motors, fan and blower sets, and the three-phase motors on feed plants and cattle-feed mixers. Any make — the job is defined by the winding in front of us, not by the badge on the end shield.

What actually happens on the bench

The winding is megged to earth and checked phase to phase before anything is touched, so the fault is known rather than assumed. Then the old coils are counted out — turns per coil, wire gauge, coil pitch, number of circuits, star or delta — and written on the job card. The stator is stripped, the slots cleaned back to bare lamination and re-lined with fresh insulation paper. New coils are wound to the recorded data, inserted, laced, connected and tested for continuity and balance. It is varnished, oven-cured, fitted with new bearings, and the rotor checked for balance and shaft wear.

What we will tell you not to rewind

Not every burnt motor is worth the copper. If the laminations have burnt and lost their insulation the core will run hot whatever winding goes into it. If the shaft is scored at the bearing seat or the end shield housing has worn oval, the new bearings will not last the season. We say so and price a replacement instead, because a rewind that fails in month four costs you more than the one you did not buy.

How it is priced

On the copper it takes and the labour to put it in — so it follows the HP, the pole count and the wire gauge, not a flat rate per motor. That is why the figure comes after we have opened the terminal box and megged it, and before anything is stripped.

Before you call

Read the nameplate, and we can quote without you moving the motor

3~ INDUCTION MOTOR

IS 12615

OUTPUT
5.5 kW / 7.5 HP
VOLTS
415 V
AMPS
11.5 A
R.P.M.
1440
PH / HZ
3 PH / 50
FRAME
132 S
INS. CL
F
CONN.
DELTA
ENCL.
IP 55
SR. NO.
XXXXXXX / 2019

A typical three-phase plate. Yours will use some of these words and not others — send the photo and we will read it.

Send a nameplate photo on WhatsApp
  • kW / HP

    Sets the copper and the price

    What the motor delivers at the shaft — not what it draws from the supply. 1 HP is 0.746 kW.

  • Volts

    Decides the connection

    415 V across three phases, or 230 V single phase. Some plates show both a star and a delta voltage.

  • Amps

    What your starter must be set to

    Full load current — what it should draw when it is working properly at rated load.

  • RPM

    Sets the pole count and the winding

    Speed on load. 2880 is 2-pole, 1440 is 4-pole, 960 is 6-pole, 720 is 8-pole.

  • Phase / Hz

    Decides the whole winding layout

    1 ph or 3 ph, and 50 Hz on any Indian supply.

  • Frame

    How a replacement is matched

    The mounting dimensions — 80, 90L, 100L, 112M, 132S and so on. It is a size, not a model.

  • Ins. class

    Sets the wire and varnish we use

    B, F or H — the temperature the winding insulation is built to survive.

  • Conn.

    Wrong one burns the winding

    Star or delta, and sometimes both with a changeover. Your starter has to agree with it.

  • IP / encl.

    Says where it can be mounted

    How well it is sealed against dust and water. IP55 on most farm and mill duty.

  • Serial / date

    Tells us its age and history

    The maker’s own reference and, on most plates, the year it was built.

Plate burnt off or missing?

It happens on older motors, and it is not a problem. Bring it in: the winding data can be counted out of the stator as the old coils come off — turns, gauge, pitch and connection — and that is what we would have wound to anyway. Send a photo of the whole motor and the terminal box instead, and tell us what it was driving.

Bring it in, or we will come to it

Walk in with the motor, send a photo of the nameplate on WhatsApp, or call and we will come out. Breakdowns are looked at the same day where we can.